Fleet Coat 30
Manufacturer: ICB (Waterproofing) Limited
Materials: Poly Methyl Methacrylates (PMMA)
Fleet Coat 30 comprises the following components:
• Fleet Coat 30 — a two-component polymethyl methacrylate waterproofing resin available in slate grey (RAL 7016). Other RAL colours are available on request
• Fleet Junction — a thixotropic version of the standard resin, for use in detailing at upstands, corners, connections and other details, available in slate grey (RAL 7016). Other RAL colours are available on request
• Fleet Coat LT — a low-temperature installation version of the standard resin, with a modified cure system, to allow application between +25 and –15°C, available in slate grey (RAL 7016). Other RAL colours are available on request
• Fleet 105 Fleece — a 1.10 kg·m–2 polyester fleece for use as a reinforcement
• Fleet Primer A2 — a non-pigmented primer based on a two-component fast-reactive polymethyl methacrylate resin, for the preparation of asphaltic and bituminous substrates
• Fleet Primer P — a non-pigmented primer based on a two-component fast-reactive and fast-curing polymethyl methacrylate resin, for the preparation of absorbent substrates such as concrete, screeds and timber
Number: 16/5326
Issue date: 20/09/2023
Approved for use on
Flat Roofs Green Roofs Pitched Roofs Roof Gardens Zero Falls Buried Roofs
For use on flat, zero fall and pitched roofs with limited access, including green roof and roof garden specifications.
Substrate
Concrete Metal Plastic Reinforced Bituminous Membranes Timber
Fleet Coat 30 is satisfactory for use as waterproofing system on flat and pitched roofs with limited access, on substrates of:
• concrete
• bituminous
• timber
• metal
• plastic
Durability
25 Years
Fleet Coat 30 will achieve a service life in excess of 25 years.
Installation Requirements
The system should only be installed by installers who have been trained and approved by the Certificate holder.
Fire Safety
A system, installed on a flat roof, comprising a 12 mm thick gypsum glassrock roof board, primed with Fleet Primer P and coated with Fleet Coat 30 (grey) reinforced with Fleet 105 Fleece, will be unrestricted by the national Building Regulations.
In the opinion of the BBA, a roof garden incorporating the system covered with a drainage layer of gravel 100 mm thick and a soil layer of minimum 300 mm thick, will be designated BROOF(t4).
In the opinion of the BBA, when the system is used in irrigated roof gardens its use will be unrestricted under the requirements of the national Building Regulations.
If allowed to dry, plants used in a roof garden may allow flame spread across the roof. This should be taken into consideration when selecting suitable plants.
The designation of other specifications should be confirmed by: England and Wales — test or assessment in accordance with Approved Document B, Appendix A, clause A1 Scotland — test to conform to Mandatory Standard 2.8, clause 2.8.1(1)(2) (1) Technical Handbook (Domestic). (2) Technical Handbook (Non-Domestic). Northern Ireland — test or assessment by a UKAS-accredited laboratory, or an independent consultant with appropriate experience.
-
Downloads
-
Fleet Coat 30 BBA 16/5326
Document class :
Document type : Link
-
ICB (Waterproofing) Limited
Unit 9-11 Fleets Industrial Estate
Willis Way
Poole
BH15 3SU